HJ-Eco Series (Eco-Gas Insulated RMU)

The HJ-Eco Series is a 12 kV ring main unit that uses dry air or N2 as the insulating gas and vacuum switching, without SF6 in the primary circuit. C, F and V modules are available, with catalogue rated currents up to 1250 A and short-circuit withstand ratings up to 31.5 kA.

HJATIS HJ-Eco environmentally considerate gas-insulated ring main unit lineupHJATIS

PUBLISHED PRODUCT DATA

Catalogue ratings and configurations.

The project data sheet should state the selected rating, options and site conditions.

01

Module Technical Specifications Matrix

Module Technical Specifications Matrix
Technical ParameterC-Module / (Load Break Switch)F-Module / (Switch-Fuse Combo)V-Module / (Vacuum Circuit Breaker)
Rated Voltage (Ur)12kV
Rated Current (Ir)630A125A630A / 1250A
Power Frequency Withstand Voltage (1 min)42kV (Phase/Earth) / 48kV (Across isolation gap)
Lightning Impulse Withstand (BIL)75kV (Phase/Earth) / 85kV (Across isolation gap)
Short-Time Withstand Current (4s)25kA-25kA / 31.5kA
Peak Withstand Current63kA-63kA / 80kA
Rated Short-Circuit Breaking Current-31.5kA (Fuse link limit)25kA / 31.5kA
Active Load Breaking Current630A--
Mechanical Endurance (Operations)5,0005,00010,000
Arc Extinguishing TechnologyVacuum Interrupter
Operating Gas Pressure (20°C)0.025 MPa (Micro-positive pressure)
Protection Degree (Tank / Enclosure)IP67 (Gas Tank) / IP4X (Outer Enclosure)

CONFIGURATION

Select your configuration.

Tell us which ratings and options you need.

ParameterCatalogue indicationProject input required
01Rated Voltage12kVSystem voltage
02Rated Current630A / 1250A (V-module)Load current requirement
03Short-Time Withstand Current (4s)25kA / 31.5kA (V-module)Fault level
04Mechanical Endurance5,000 / 10,000 operationsExpected switching frequency
05Protection DegreeIP67 (tank) / IP4X (enclosure)Installation environment

STANDARDS & REPORTS

Standards and product documents.

Applicable references: GB/T 3906 and IEC 62271-200. Ask for the edition and reports covering the model offered; a standard number alone does not confirm product compliance.

PRODUCT DOCUMENTSProduct documents available

Check the model and ratings in the documents below.

View documents ↓
Compare GB and IEC references ↗Your StandardBridge inputs and results are not attached to a sales enquiry automatically.

APPLICATIONS

Questions for your application.

01

Utility and industrial distribution

What are the feeder rating and fault level at the installation point? Send the protection scheme with the enquiry.

02

Renewable-energy collection networks

Will the device switch cables, transformers or other plant loads? State the switching duty and required control signals.

TECHNICAL LIBRARY

Product documents

Check the tested model and ratings before using a report for your project.

All documents
Test report2023

HJ-Eco — Test report

Reported model HJHB-12PT/630-20

12 kV / PT unit / 20 kA

Tests on the dry-air voltage-transformer cabinet. Not a report for every RMU functional unit.

48 pages·3.4 MB·English guide + Chinese original

Test report2023

HJ-Eco — Test report

Reported model HJHB-12V/630-20

12 kV / 630 A / 20 kA

Dry-air, top-extension arrangement. This report does not establish an internal-arc classification.

55 pages·4.1 MB·English guide + Chinese original

The English guide is prepared by HJATIS; it is not a laboratory translation or an IEC certificate. Results apply to the tested sample and configuration. The original report and its stated standard editions govern.

REQUEST A QUOTATION

Send the SLD, specification or BOQ.

Include the system voltage, fault level, service conditions and delivery scope for a model selection and document list.